IMS-REL: Error Relais Module
Key Features
- Monitoring the synchronization status of the used receivers
- Optional: monitoring of PPS, 10 MHz, events (notifications)
- Three-year warranty
Product Description
If the internal hardware clock is running synchronous to the source, the relay is switched to NO (Normaly Open) mode. In case of an error, the relay switches to NC (Normaly Closed) mode.
Depending on the hardware configuration of the IMS system, i.e. redundant with RSC module and two integrated reference clocks or with SPT module and only one reference clock, different relay states can be switched.
In redundant operation, the two clocks and the changeover unit are monitored as standard (CLK1 - relay A, CLK2 - relay B, RSC - relay C).
Optionally, other signals can also be monitored (10 MHz, PPS). The relays A + C can also be switched by notifications (events).
Characteristics
Status Indicators | All LEDs red: Outputs disabled
All LEDs green: normal operation, outputs enabled Single LED red: Indicates a faulty output or short circuit during normal operation. |
Operating Voltage | +5 V DC |
Supported Temperature | Operational: 0 - 50 °C (32 - 122 °F)
Storage: -20 - 70 °C (-4 - 158 °F) |
Supported Humidity | Max. 85 % (non-condensing) at 40 °C |
Warranty | Three-year warranty |
RoHS Status of Product | This product is fully RoHS-compliant. |
WEEE Status of Product | This product is handled as a B2B (Business to Business) category product. To ensure that the product is disposed of in a WEEE-compliant fashion, it can be returned to the manufacturer. Any transportation expenses for returning this product (at end-of-life) must be covered by the end user, while Meinberg will bear the costs for the waste disposal itself. |