FDM511: Frequency Deviation Monitor for 50/60Hz power line networks
Key Features
- Monitoring of Mains Frequency
- Pre-connected GPS, GLN or PZF Receiver as Reference
- 2 analog outputs (time deviation and/or frequency deviation)
- 5mm LED Display (optional)
- Serial RS232 Interface
- Calculation of Time based on the Local Frequency
-
Previous Models - FDM511:
FDM509 :: Frequency Deviation Monitor for 50/60Hz power line networks
Product Description
A preconnected reference is necessary that provides a high accuracy 10MHz clock, a serial time string and a PPS (pulse per second). The accuracy of the measurements is derived from these signals.The module calculates the frequency as well as the time, based on the mains frequency. The time deviation (TD) is the difference of this calculated time (PLT) to the reference time (REF). This time deviation as well as the frequency itself is sent out via serial interface or is beeing converted to an analog voltage output provided by a DAC.
The board is equipped with a flash memory and a bootstrap loader which allows to update the systems firmware via serial port.
Please note: the shown variant of the FDM511 is equipped with an optional LED display, the standard version of the FDM511 comes without this display!
Characteristics
Display | 8-digit alphanumeric dot matrix display, digit size 5 mm |
Input signal | 10MHz, serial time string (via COM1), PPS mains frequency, 70 - 270VAC, 50Hz or 60Hz |
Interface | Two asynchronous serial RS232 ports, COM0 and COM1 Baudrate: 600, 1200, 2400, 4800, 9600, 19200 Baud Framing: 7N2, 7E1, 7E2, 8N1, 8N2, 8E1, 7O2, 8O1 output and average: once per second Output string: The frequency, frequency deviation, reference time, power line time and the time deviation are send out in one of three available formats. The formats are:
STANDARD FDM String:
SHORT FDM String:
AREVA FDM String: |
Resolution of Measurement | frequency: accuracy of reference (10MHz) ±1mHz time deviation: accuracy of reference (PPS) ±1ms |
Analog outputs | 2 analog outputs for longtime-recording (time deviation and/or frequency deviation), range: -2.5V ... +2.5V, resolution: 16Bit |
Dimensions of the front panel | without display: 8HP/3U (40mm x 128mm) with display: 12HP/3U (60mm x 128mm) |
Electrical Connectors | rear VG edge connector, mixed F/H, DIN 41612, Type F: 24 pin, type H: 7 pin optional mains socket in the front panel |
Operating Voltage | +5 V DC |
Current Draw | 180 mA |
Board type | Eurocard |
Board Dimensions | 160 mm x 100 mm, 1,5 mm Epoxy |
Supported Temperature | Operational: 0 - 50 °C (32 - 122 °F)
Storage: -20 - 70 °C (-4 - 158 °F) |
Supported Humidity | Max. 85 % (non-condensing) at 40 °C |
Warranty | Three-year warranty |
Options | Eight character, 5mm height, dot matrix LED display for showing the measurements and configuration 10/100 BaseT Ethernet connection (RJ45) for measurement monitoring via the network power line input via mains socket in the front panel external large display for showing the measurements of a FDM511: DU35K/FDM |
RoHS Status of Product | This product is fully RoHS-compliant. |
WEEE Status of Product | This product is handled as a B2B (Business to Business) category product. To ensure that the product is disposed of in a WEEE-compliant fashion, it can be returned to the manufacturer. Any transportation expenses for returning this product (at end-of-life) must be covered by the end user, while Meinberg will bear the costs for the waste disposal itself. |